A vapor-compression refrigeration cycle operates at steady state with Refrigerant 134a as the working fluid. Saturated vapor enters the compressor at 2 bar, and saturated liquid exits the condenser at 8 bar. The isentropic compressor efficiency is 80%. The mass flow rate of refrigerant is 7 kg/min.

1-Write the assumptions no less than three

2-Draw clear Schematic

(3) the compressor power, in kW.

(4) the refrigeration capacity, in tons.

(5) the coefficient of performance.

Respuesta :

Answer:

(3) the compressor power, in kW. = 4.17KW

(4) the refrigeration capacity, in tons.= 4.905tons

(5) the coefficient of performance. = 4.1336

check attached files for other answers.

Explanation:

Ver imagen adebayodeborah8
Ver imagen adebayodeborah8